New York City is in the grip of an almost unprecedented heatwave, and with it what is becoming a seemingly annual outbreak of Legionnaires disease in the Big Apple. The current outbreak has resulted in 82 cases of Legionnaires’ disease (sadly causing 5 deaths). Officials have confirmed 56 cooling tower systems have tested positive for Legionella.

Hot summers are delivering annual outbreaks of Legionnaires Disease in New York City
To the layperson, outbreaks during periods of extreme summer heat make sense; the adaptable Legionella bacteria that causes the disease thrives in warm, stagnant water and is present in a temperature range between 20°C and 45°C, with optimal temperatures between 25°C to 45°C.
In Australia it is not uncommon for a building’s cooling system to remain dormant during the cooler winter months. Hydrochem CEO Nick Duncan has reinforced the need for a controlled, measured approach to restarting equipment as we transition from winter to spring.
“In Australian climates, we need to think of spring as the start of our ‘Legionella season’”, he says. “As the warmer weather commences, inactive systems start up for the first time and there is a very real risk there may have been stagnation in the cooling water system.”
Stagnant water in a cooling system poses a high risk of Legionella growth. Chemicals may not have been distributed throughout the system, and tests that have been conducted may not be representative. If such systems are simply started up in early spring they are at risk of introducing Legionella into the air in the form of an aerosol.
“Mitigating this risk is important,” says Duncan.
“In most states, regulations require any system that has been inactive for a period to be treated. Where it is not a requirement, it should certainly be seen as best practice.”
Hydrochem CEO Nick Duncan
Ideally, stagnancy is avoided by circulating systems every 48 hours. Circulating cooling water systems is the first step as this ensures a good turnover of water.
Other steps in the process that mitigate the risks involved at startup include:
- Disinfecting the water circulating in the system
- Conducting a thorough, interior clean on each cooling tower
- Adding a chlorine-compatible bio-dispersant to the circulating water
“Legionnaires disease is a preventable public health risk,” concludes the Hydrochem CEO. “It strikes at the immuno-compromised members of our communities and poses a potentially lethal risk to this vulnerable group of people.”